FLOODED DEEP CYCLE BATTERY |
2 YS 27P |
|
|
| Series | FLA SERIES 5000 | Warranty | 5 Years |
|---|---|---|---|
| Volts | 2 | Design | SPEC |
| Cells | 1 | Plates/Cell | 27 |
| Terminal Type | Flag | ||
| Included Hardware | S/S Hex Cap Screw, Nut, Lock & Flat Washer | ||
| Size & Thread | 5/16"-18 | ||
| Cables | 19" 4/0 interconnect cables *RE incl. | ||
| Charge | Discharge | |
|---|---|
| Charge Voltage Range | 2.45-2.5 V/cell @ 25°C (77°F) |
| Float Voltage Range | 2.25 V/cell @ 25°C (77°F) |
| Self-Discharge Rate | 5%-10% per month at 25°C (77°F) |
| Capacity | |
|---|---|
| Cold Crank Amps (CCA) 0°F / -18°C | 4975 |
| Marine Crank Amps (MCA) 32°F / 0°C | 6219 |
| Reserve Capacity (RC @ 25A) | 5257 Minutes |
| Reserve Capacity (RC @ 75A) | 1752 Minutes |
| Capacity Affect by Temperature | 40°C (104°F) |
25°C (77°F) |
0°C (32°F) |
-15°C (5°F) |
|---|---|---|---|---|
| 105% | 100% | 75% | 50% |
| Hour Rate | Capacity / AMP Hour | Current / AMPs |
|---|---|---|
| @ 100 Hour Rate | 2825 AH | 28.25 A |
| @ 72 Hour Rate | 2672 AH | 37.11 A |
| @ 50 Hour Rate | 2530 AH | 50.59 A |
| @ 20 Hour Rate | 2190 AH | 109.51 A |
| @ 15 Hour Rate | 2037 AH | 135.79 A |
| @ 10 Hour Rate | 1949 AH | 194.93 A |
| @ 8 Hour Rate | 1884 AH | 235.45 A |
| @ 5 Hour Rate | 1752 AH | 350.44 A |
| @ 1 Hour Rate | 986 AH | 985.61 A |
| Specifications | |||
|---|---|---|---|
| Weight | 111.5 kg | 246 lbs | |
| Length | 356 mm | 14" | |
| Width | 229 mm | 9" | |
| Height Incl. Term. | 803 mm | 31.63" | |
| Product measurements & weights are calculated based on sample data. Individual specifications are subject to vary due to the manufacturing process & battery components. | |||
| Electrolyte Reserve | 95 mm | 3.75" | |
|---|---|---|---|
| Container (Inner) | Polypropylene | ||
| Cover (Inner) | Polypropylene - heat sealed to inner container | ||
| Container (Outer) | High Density Polyethylene | ||
| Cover (Outer) | High Density Polyethylene snap fit to outer container | ||
| Handles | Molded | ||
|
|||
Cycle Life vs. Depth of Discharge
Voltage vs. Depth of Discharge