FLOODED DEEP CYCLE BATTERY

16 CH 33P

Series 5000 Warranty 5 Years
Volts 32 Design SLI
Cells 16 Plates/Cell 33
Terminal Type Paddle RR
Charge
Charge Voltage Range 2.45-2.5 V/cell @ 25°C (77°F)
Float Voltage Range 2.25 V/cell @ 25°C (77°F)
Self-Discharge Rate 5%-10% per month at 25°C (77°F)
Capacity
Cold Crank Amps (CCA) 0°F / -18°C 2754
Marine Crank Amps (MCA) 32°F / 0°C 3443
Reserve Capacity (RC @ 25A) 2198 Minutes
Reserve Capacity (RC @ 75A) 733 Minutes
Hour Rate Capacity / AMP Hour Current / AMPs
@ 100 Hour Rate 1053 AH 10.53 A
@ 72 Hour Rate 1026 AH 14.25 A
@ 50 Hour Rate 989 AH 19.79 A
@ 20 Hour Rate 916 AH 45.80 A
@ 15 Hour Rate 861 AH 57.40 A
@ 10 Hour Rate 824 AH 82.44 A
@ 8 Hour Rate 788 AH 98.47 A
@ 5 Hour Rate 733 AH 146.56 A
@ 1 Hour Rate 431 AH 430.52 A

Ampere hour capacity ratings based on specific gravity of 1.280 at 27°C (80°F).
Reduce capacities 5% for specific gravity of 1.265 and 10% for 1.250.

Specifications
Weight 729.5 kg 1608 lbs
Length 1092 mm 43"
Width 699 mm 27.5"
Height Incl. Term. 514 mm 20.25"
Product measurements & weights are calculated based on sample data. Individual specifications are subject to vary due to the manufacturing process & battery components.
Electrolyte Reserve 95 mm 3.75"
Container (Inner) Polypropylene
Cover (Inner) Polypropylene - heat sealed to inner container
Container (Outer) High Density Polyethylene
Cover (Outer) High Density Polyethylene snap fit to outer container
Handles None
Compatible with Flow-rite single-point watering system for locomotive batteries
  • Plastics are UL94 HB (UL94-V2 available)
  • Plastics are impact copolymer rated to ASTM D256, D5420
  • Vented design with integral flame arrestor vent caps

Cycle Life vs. Depth of Discharge

Detailed Illustration

Rev.#6 | August 2024